AN3530 Speed Monitoring Protector
AN3530 Speed Monitoring Protector
Classification:
Product Description
Technical data
1. Sensor requirements:
Magnetoelectric sensor: passive type, output pulse signal with the proportion of speed and frequency; The installation gap is 1mm±0.2mm.
Magnetoresistive sensor: active type, output TTL level signal with the proportion of speed and frequency; Installation clearance: 2.5mm±0.5mm.
Eddy current sensor: sensitivity: 7.87 mV/μm (200 mV/mil), GAP voltage: -10 VDC.
Note: The installation clearance is determined by the mechanical distance of 1mm between the tooth top and the probe or the output voltage of the preamplifier -10VDC, and the mechanical distance is given priority to avoid damage to the probe caused by the eccentricity of the rotating shaft.
2. Measuring range:
Standard speed: Range: 0~9999rpm, Accuracy: ±0.5%±1 rpm
Zero speed: Range: 0~99.99rpm, accuracy: ±0.5%±0.01rpm
Note: The range can be programmed on site.
3. Power supply:
DC power supply: 24VDC (18~36V);
AC power supply: 220VAC(165~260)/47~63Hz;
AC power supply: 110VAC /47~63Hz;
Power consumption: 5W.
4. Standard signal output:
Standard current: 4~20mA (corresponding to the upper limit of full scale)
Active: Drive load: ≤500Ω, effective transmission distance: ≤ 300 m (1000 ft).
5. Relay output:
Two-stage threshold (Alert, Danger) programmable setting and normally open and normally closed dry contact output, the full scale range can be set, and the error is ≤0.1%;
Insulation resistance: ≥1000MΩ;
Contact capacity: 2A/30VDC, Double Pole Double Throw (DPDT);
Alarm delay: 0.1 to 60S, default value: 0.5S;
Alarm Latching: The default is non-latching.
6. Physical characteristics:
Dimensions (LxWxH): 120mm×70mm×80mm;
Weight: 0.8Kg.
7. Installation:
Standard rail mounting: DIN 35mm;
Base plate mounting: 100mm×80mm.
8. Environmental restrictions:
Operating temperature: -30°C~+65°C;
Storage temperature: -40°C~+85°C;
Relative humidity: 0~95% non-condensing.
9. Refer to the implementation standards
American Petroleum Institute API 670 standard;
Safety Certification: C E;
Degree of protection: IP56;
Immunity to electromagnetic interference: EMC\LVD with reference to EN55011\EN 61010\EN50081\EN50082.
Product selection
AN3531/32—Rotational speed/zero rotational speed/keyphase
AN 3531- AXX-BXX-CXX-DXX-EXX-FXX
AN 3532- AXX-BXX-CXX-DXX-EXX-FXX
AN 3533- AXX-BXX-CXX-DXX-EXX-FXX
Standard Models:
Speed: AN3531-00-00-00-00-00-00-00-60
Zero speed: AN3532-00-01-00-00-00-00-00-60
Key phase: AN3533-00-01-00-02-00-00-01
A: Measuring range
00-0~9999rpm standard
01—0~99.99rpm zero speed
02—Others (Remarks)
Note: The range can be programmed on site.
B: Type of external sensor
00—Passive magnetoelectric probe
01—Active magnetoresistive probe
02—Proximity current sensor (φ5/φ8 diameter probe)
03—The same type of probe from other manufacturers
Note: Magnetic probes are recommended for standard speeds, and active magnetoresistive probes or eddy current probes (φ8/φ5 diameters) are used at zero speeds.
C: Relay output (DPDT):
00—Two dry contact outputs (Alert, Danger)
01—Single Dry Contact Output (Alert)
02—No relay output
D: Standard Signal Output:
00—4~20mA standard current output
01—1~5V standard voltage output
02—RS 485 communication interface output
03—Others
E: Power supply
00—24VDC(18~36V)
01—220VAC
02—110VAC
03—Others
F: Installation
00—DIN 35mm for rail mounting
01—bottom plate installation
G: Number of teeth (number of keys or slots)
01—1 pc
60-60 pcs
XX—Others (the number of teeth in this option represents the number of teeth)
Note: If you select other options for the model option, please note the description. For details, please contact the company's technical support department.
Previous Page
Next Page
Previous Page
Next Page
Related Products
Online message